Trust Us

AVVG / АВВГ - power cables

Technical Specifications

  • in accordance with GOST 1508-78;
  • ultimate operating temperature in fixed (immovable) condition is from - 40°С upto +50°С;
  • rated voltage with frequency of up to 100Hz U=0.66 kV; Uconst.=1kV;
  • testing voltage, AC, frequency 50Hz - 2,5kV;
  • electrical resistance of conductive core in accordance with GOST 22483;
  • minimal bending radius not less than 3 cable diameters for a cable with outer diameter of up to 10mm inclusively; not less than 4 cable diameters with outer diameter 10-25mm;
  • factory length, not less than 150m.

Cables Structure

AVVG

  • copper conductive core in accordance with GOST 22483-77 and TU 3518 PK 4043838373-TOO-17-2003;
  • PVC core insulation in accordance with GOST 5960-72;
  • insulated cores are twisted;
  • cores color in accordance with GOST 1508-78;
  • PVC compound cover in accordance with GOST ГОСТ 5960-72;
  • cover color - black.

Application

Cables are used for immovable connection to electrical devices and apparatus – for laying indoors, channels, tunnels, in corrosive medium without mechanical impact on a cable.

Order arrange table

Type

Number of cores

Voltage

0,66 kV

1 kV

6 kV

Nominal cross-section, mm2

AVVG

1, 2, 3, 4, 5, 6

2,5-50

2,5-240

-

3

-

-

10-240

 

Voltage , kV

Nominal cross-section

Cable shipping length, m, not less

to 1 inclusive

1,5-16
25-70
95 and higher

450
300
200


6

10-70
95-120
150 and higher

450
400
350