Trust Us

APV / АПВ - PVC insulated wire for electric facilities (aluminum core)

Technical Specifications

  • Wires with PVC insulation for electric installations are according to GOST 6323-79 (State Standard);
  • Maximum working temperature of APV wire under conditions of fixed mounting is from -400C to +700;
  • Electric resistance of APV wire lead core is according to GOST 22483-77;
  • Maximum operational temperature of the APV wire is +70°C;
  • Electric resistance of wire insulation at +20°С, 1 km length is not less than 1 milliOhm;
  • Minimal bending radius of APV cable while mounting is not less than five times over minimum outer diameter of the wire;
  • AC Testing voltage at frequency 50 Hz is 2,5 Kv;
  • Service life period of APV cable is not less than 15 years.

Construction wire

  • Aluminum soft core of APV wire made according to TU 16.К71-087 (Company Standard);
  • Insulation of the wire is made from PVC elastron according to GOST 5960-72 (State Standard);
  • APV wire insulation colored according to GOST 6323-79 (State Standard).

Applications

According to GOST 6323-79 (State Standard) APV wire is applied to electric installations at fixed construction in power and illuminating networks and also for mounting electric equipment, machines and tools at rated voltage 450 V (up to 450/750 V for networks) with frequency up to 400 Hz or up to 1000 V direct voltage.

Order arrange table

Grade of wire

Nominal section of wire, mm2

Outside diameter of wire, mm (no more than)

Nominal weight of 1 km of wire, kg

Factory length, m

APV 1,5

1,5

3,3

12,5

100

APV 2,5

2,5

3,9

15,5

APV 4

4,0

4,4

21

APV 6

6,0

4,9

28,5

APV 10

10,0

6,4

47

APV 16

16,0

8,0

66

APV 25

25,0

9,8

114

APV 35

35,0

11,0

146

APV 50

50,0

13,0

202

APV 70

70,0

15,0

266

APV 95

95,0

17,0

366

Support request