Trust Us

AKVVG, AKVVGe, KVVG, KVVGe / АКВВГ, АКВВГэ, КВВГ, КВВГэ – Control Cables

Technical Specifications

  • in accordance with GOST 1508-78;
  • ultimate operating temperature in fixed (immovable) condition is from - 40°С upto +50°С;
  • rated voltage with frequency of up to 100Hz U=0.66 kV; Uconst.=1kV;
  • testing voltage, AC, frequency 50Hz - 2,5kV;
  • electrical resistance of conductive core in accordance with GOST 22483;
  • minimal bending radius not less than 3 cable diameters for a cable with outer diameter of up to 10mm inclusively; not less than 4 cable diameters with outer diameter 10-25mm;
  • factory length, not less than 150m.

Cables Structure

KVVG

  • copper conductive core in accordance with GOST 22483-77 and TU 3518 PK 4043838373-TOO-17-2003;
  • PVC core insulation in accordance with GOST 5960-72;
  • insulated cores are twisted;
  • cores color in accordance with GOST 1508-78;
  • PVC compound cover in accordance with GOST ГОСТ 5960-72;
  • cover color - black.

KVVGe

  • the same, in overall alumina-polymeric screen.

AKVVG

  • alumina conductors, PVC insulation, PVC cover.

AKKVGe

  • the same, in overall alumina-polymeric screen.

Application

Cables are used for immovable connection to electrical devices and apparatus – for laying indoors, channels, tunnels, in corrosive medium without mechanical impact on a cable.

Order arrange table

Type

Nominal cross-section, mm2

0,75

1,0

1,5

2,5

4,0

6,0

10

Number of cores

AKVVG

-

4, 5, 7, 10, 14, 19, 27, 37

4, 7, 10

KVVG
KVVGe

4, 5, 7, 10, 14, 19, 27, 37, 52, 61

4, 5, 7, 10, 14, 19, 27, 37

4, 7, 10

-

Support request

Support request