Trust Us

A, AS / А, АС – non-insulated wires for aerial transmission lines


Technical Specifications

  • Non-insulated wires for aerial transmission lines correspond to GOST 839-80 (State Standard);
  • Wire weight, resistance and breaking strength are shown in Table 1.

Structure of wire A

  • The wire consists of smaller aluminum wires, stranded by right unidirectional concentric strand with strand direction of adjacent layers to opposite sides and outer layer has a right direction.

Structure Wire AS

The wire consists of steel support core and aluminum wires, stranded by right unidirectional concentric strand with strand direction of adjacent layers to opposite sides and outer layer has a right direction.

Applications

A and AS non-insulated wires proposed for transferring energy through aerial overhead transmission in atmosphere of air of types I and II under condition of the maintenance in atmosphere of sulphurous gas no more than 150 mg/m2 per day (1,5 mg/m3) on driest macroclimatic areas in accordance with GOST 15150 (State Standard) executions UHL, except TV and the TS. Wires are not insulated mainly are used for electric mains, on substations and switching centers, for lines of the electrified transport, in distributive chains of electric cars and devices where as an insulator the air environment is used. Not insulated aluminum and steel-aluminum wires are made according to GOST 839-80 (State Standard). Steel-aluminum wires find the widest application for a construction high-voltage power lines with the big flights, difficult climatic conditions (ice, snow loadings, a wind) etc. Admissible prolonged current loadings on non-insulated wires depend on conditions of their operation, a place of their lining etc. Defined by GOST 839-80 (State Standard) and regulated by PUE.

Order arrange table of Wire A

Nominal Section, mm2

Section, mm2

Diameter of the wire, mm

Electric resistance at 20 ⁰C, length 1 km, DC, no more than

Breaking strength of the wire, N, not less

Weight of 1 km of the wire, kg

10

10,0

4,05

2,8631

1950

27,4

16

15,9

5,10

1,8007

3021

43,0

25

24,9

6,40

1,1498

4500

66,0

35

34,3

7,50

0,8347

5913

94,0

40

40,0

8,09

0,7157

6800

109,4

50

49,5

9,00

0,5784

8198

135,0

63

63,0

10,16

0,4544

10390

172,3

70

69,3

10,70

0,4131

11288

189,0

95

92,4

12,30

0,3114

14784

252,0

Order arrange table of Wire AS

Nominal Section

Section aluminum/ steel

Diameter of the wire

Diameter of the steel support core, mm

Resistance at 200C, length 1 km, DC, no more than

Breaking strength of the wire, N, not less than

Weight of Al section, kg

Weight of the steel support core, kg

Weight of the wire, kg

(10/1,8)

10,6/1,77

4,5

1,5

2,7064

4089

28,9

13,8

42,7

(16/2,7)

16/2,69

5,6

1,9

1,7818

6220

44,0

20,9

64,9

(25/4,2)

24,9/4,15

6,9

2,3

1,1521

9296

67,9

32,4

100,3

(35/6,2)

36,9/6,15

8,4

2,8

0,7774

13524

100,0

48,0

148,0

(40/6,7)

40/6,7

8,74

2,91

0,7172

14400

109,5

51,8

161,3

(50/8,0)

48,2/8,04

9,6

3,2

0,5951

17112

132,0

63,0

195,0

(63/10,5)

63/10,5

10,97

3,66

0,4553

21630

171,4

82,6

254,0

(70/11)

68/11,3

11,4

3,8

0,4218

24130

188,0

88,0

276,0

(95/16)

95,4/15,9

13,5

4,5

0,3007

33369

261,0

124

385,0

Support request