Trust Us

Terminal box rek-10HH2-1-М for outdoor installation and rek-10HH-1-М for internal installation

for 1-core cables with insulation from vulcanized (cross linked) polyethylene for 6 and 10 kV voltage

Technical performance

rek-10HH-1-M termination is used with anti-tracking heat shrinkable tubes, applied for 1-core cables with XLPE insulation, PVC jacket, armored with steel tape or wire, the voltage up to 10 kV.

The termination kit includes:

  1. Universal tear-off head bolt connectors from GPH Company;
  2. Special tapes;
  3. Anti-Tracking heat shrinkable tubes;
  4. Anti-Tracking heat shrinkable rain sheds;
  5. Screen and armor grounding set;
  6. Installation manual.

Structure of the kit

Termination of the cores is made by tear-off head bolt lugs. Anti-tracking heat shrinkable tubes with an internal, integrated component of alignment of the electric field, is used as the main electrical insulating material.
Heat shrinkable tubes together with adhesive and special tapes provide complete sealing of the cable end termination.
Grounding of the cable’s armor is made without soldering, by special armor connection set in rek-10HH-1-M couplings.

Installation

  • Preparation of the cable made in accordance with installation manual of the coupling;
  • It is recommended to use special tools to remove the semiconducting layer from the insulation.

Application

rek-10НН-1-М termination is designed to connect outdoor and indoor termination of the 1-core cables with XLPE insulation, PVC sheath, armored with steel tape or wire.

Features

The rek-10HH-1-M type terminations correspond with ST TOO 41021646-14-2007 and meet the requirements of GOST 13781.0-86 (State Standard).

Cable type

For 1-core cables: APvEp-6/10, APvEgP-6/10, APvEgaP-6/10, PvEP-6/10, PvEgaP-6/10, PvEgP-6/10 and others (made in Russia); N2XS2Y, N2XS2Y, NA2XS2Y , NA2XSY, N2XSEY, 2XSEY, A2XSEY etc. and others (imported, TS and VDE standard).

Order arrange table for indoor installation

Nominal voltage, kV

Cross section mm2

Number of cores in the cable

Order name

Length of core termination, mm (L min)

Unarmored cables

Tape armor cables

6 и 10

50/120

1

rek-10HH-1-50/120-М

rek-10HH-1-50/120-АМ

320

6 и 10

120/240

1

rek-10HH-1-120/240-М

rek-10HH-1-120/240-АМ

330

6 и 10

300/400

1

rek-10HH-1-300/400-М

rek-10HH-1-300/400-АМ

340

6 и 10

500/630

1

rek-10HH-1-500/630-М

rek-10HH-1-500/630-АМ

350

Order arrange table for outdoor installation

Nominal voltage, kV

Cross section mm2

Number of cores in the cable

Order name

Length of core termination, mm (L min)

Unarmored cables

Tape armor cables

6 и 10

50/120

1

rek-10HH2-1-50/120-М

rek-10HH2-1-50/120-АМ

320

6 и 10

120/240

1

rek-10HH2-1-120/240-М

rek-10HH2-1-120/240-АМ

330

6 и 10

300/400

1

rek-10HH2-1-300/400-М

rek-10HH2-1-300/400-АМ

340

6 и 10

500/630

1

rek-10HH2-1-500/630-М

rek-10HH2-1-500/630-АМ

350

* The kit of coupling with wire armor cable is ordered separately.

Support request

Support request