Joint sleeves eks-10SK-L-SL-M / eks-10СК-Л-СЛ-М

for 3 lead cores cables with impregnated paper insulation for 6 and 10 kV voltage

Sleeve design

Electric field strength is equalized by special bands. Insulation of connections is made be heat-shrinkable tubes. Space between cores and between cores and jacket is filled by PU compound, which provides encapsulation of connecting cores and sealing of oil and colophony material, as well as required short circuit currency stress test indexes. External protection of the sleeve from mechanical damages is provided by structure material armocast. To protect joint places, self-conductive Band 13 and high-voltage self-vulcanizing Band 23 are bounded consequently cartridges.

Additional benefit

Joint sleeve installation can be done in excavation with no more length, than joint sleeve length. There is a possibility to install fixed joint sleeve without cable break.

Table for order

Nominal voltage, kV

Lead core cross section, mm2

Name

Size, mm

Length, (L)

Diameter (D)

6 and 10

16/25

eks-10SK-L-3-16/25-SL-M

880

70

6 and 10

35/50

eks-10SK-L-3-35/50-SL-M

960

80

6 and 10

70/120

eks-10SK-L-3-70/120-SL-M

1030

90

6 and 10

150/240

eks-10SK-L-3-150/240-SL-M

1090

105